MDH Blower HeaterCONTROL PRINCIPALS:

The temperature leaving the unit is maintained at an adjustable preset temperature. Typically, if the discharge air temperature drops below 0º C the power to the fan and element is shut off in "Low Temp" condition to prevent freezing. A timer overrides the low temperature signal for an initial period of approx. 8 minutes every time the blower heater is reset at the status board, or control power is cycled. The blower heater will automatically restart again once the temp. sensor detects 2º C or more. A high temperature sensor will cut the power to the heating elements if it senses temperatures above the normal operating range. After cooling down the elements will automatically restart if there is a demand.

CONTROL FEATURES:

Solid state controller designed and manufactured by Dexon provide the following features:

Status Info

ELECTRICAL REQUIREMENTS:

MECHANICAL REQUIREMENTS:

Power On No Air Low Temp Over Heat Element No.1 Element No.2 Element No.3 Warning Message Reset Switch Fan Switch